BASIC OPERATION OF POWER PLANT (WHRB)
POWER PLANT OPERATION
BY MUJIYONO
BOILER
Definition
As per Indian
Boiler Act 1923, Boiler is defined as any closed vessel exceeding 22.75 liters
in capacity which is used exclusively for generating steam under pressure and
includes any mounting or accessories attached to such vessel, which is wholly
or partially under pressure, when steam is shut off.
A good Boiler should have some essential qualities.
1. Capable
to meet large load fluctuations.
2. Fuel
efficient i.e. to generate maximum steam with minimum fuel consumption.
3. Ability
to start-up quickly.
4. Easy
in maintenance and inspection.
5. Occupy less floor space.
6. Lower
friction loss in water and flue gas circuit
7. Little
attention for operation and maintenance.
Systems in a Boiler
A Boiler mainly
contains following systems :
1. Feed
water system.
2. Steam
system.
3. Air
system.
4. Flue
gas system.
5. Fuel
handling system.
6. Ash
handling system.
Boiler Mountings
Fittings
on a Boiler which are required for its safe and efficient operation are called mountings.
These are as follows :
1. Safety
valve
2. Water
level sight glass (gauge glass)
3. Pressure
gauge
4. Blow
down valve
5. Main
steam stop valve
6. Feed
water check valve (NRV)
7. Air
Vent
8. Start-up
vent
9. Manhole
Boiler Accessories
The devices which are used in a Boiler
as an integral part and help to run the Boiler efficiently are called Boiler Accessories. These are :
1. Super
heater
2. De-super
heater
3. Economizer
4. Air
Pre-heater
5. Soot
Blower
6. Feed
Pump
7. ID
and FD fans
8. Ash
Removal system
9. Fuel
supply system
10. Dosing
system
11. Deaerator
Steam
Generation In A Boiler..contd
In
a Boiler fuel is burnt to get heat energy which is converted from chemical
energy stored in a fuel. This heat energy is utilized to produce steam from
feed water.
Fuel
is fired in the furnace of the Boiler. Different fuel is used in different
Boilers. Accordingly furnace is designed. Water tubes are arranged around the
furnace and flue gas path. Water tube arrangement made around the furnace is
called as water wall. Feed water is circulated in these tubes. Water comes to
water wall from Boiler drum, and circulated back to drum after absorbing heat.
Due to difference in density which is created due to difference in temperature,
water circulates in these tubes naturally. Therefore, it is called Natural
Circulation.
During
circulation of water in tubes, steam is generated and collected at the upper
part of the Drum. This is called Saturated Steam corresponding to Boiler drum
pressure. This steam is further heated in Superheaters and becomes superheated
steam.
Boiler
Drum is filled with fresh feed water. The feed water, before entering into drum
is heated at Economizer. Economizer is placed at the flue gas path. Most of the
heat of the flue gas is utilized inside the Boiler. Still considerable amount
of heat energy is available in it. This heat is utilized in Economizer to heat
up the feed water.
For
burning of fuel, required Oxygen is obtained from atmospheric air. Air is
required in Boiler furnace for combustion. This is supplied by Forced Draught
(FD) fan. This air is heated at air pre-heater (APH) before being sent into
furnace. If cold air is used then there will be loss in energy. Air pre-heater
is placed at the flue gas path after Economizer. Air pre-heater is a heat
exchanger which exchanges the heat of flue gas to the cold air, which is to be
used in furnace. By heating the air, burning of fuel is easier and loss of
energy is minimized. If hot flue gas would not be used to heat up feed water at
Economizer and air at Air Pre-heater then it would escape into atmosphere.
Finally
the flue gas passes through Electrostatic Precipitator (ESP) and exhausted to
atmosphere through chimney. At ESP the dust particle in the flue gas is trapped
and clean gas escapes to atmosphere.
Ash
which is produced in the Boiler due to combustion of solid fuel is collected at
Boiler bottom and also in Economizer, Air Pre-heater and ESP. This ash is
disposed off with the help of suitable ash handling system.
Preparations for Cold Start-up
1. All
the manhole doors should be in close condition. Tightness of the Nuts and Bolts of the man
hole doors to be checked properly.
2. All
the water wall drain lines should be in close condition.
3. All
the steam drain lines should be in open condition.
4. Start-up
vent Root Manual isolation valve should
be in open condition.
5. Drum
level should be at Normal Water Level (NWL).
6. Continuous
Blow Down (CBD) and Intermittent Blow Down (IBD) drains should be
in close condition.
7. All
the super heater vents including Drum vent and Puppy Header vent should be in
open condition.
8. Before
and After Isolation valves at Feed Control Station (FCS) should be in open
condition.
9. Attemperation
Control valve before and after isolation valve should be in open condition .
10. Hydra
step should be in healthy condition.
11. Safety
valves should be in healthy condition.
12. Main
Steam stop valve and by- pass valve should be in close condition.
13. Soot
blower manual isolation valve and control valve should be in close condition.
14.Boiler
Drum Gauge glass steam side and water side isolation cocks should be in open
condition.
15. HP
Dosing Pumps should be in Healthy condition and open suction and discharge
valves of the pump.
16. Solution
in HP Dosing agitator tank should be at normal level.
17. Boiler
Feed Pumps should be in healthy condition.
18.Deaerator
water level should be maintained at 60% by taking DM Transfer pump in service.
19. Air
compressors should be in healthy condition.
20. Ash
handling systems should be in healthy condition.
21. ESP
should be in healthy condition.
22. ID
fan damper should be in Zero position.
23. All
the interlocks and protection should be checked properly viz. Drum level low,
Deaerator level low, Boiler Feed Pump (BFP) discharge pressure low, Flue gas
temperature at Post Combustion Chamber (PCC) outlet high, silo level.
Cold Start-up process
1. After
Kiln light-up, when flue gas temperature at PCC outlet increases to more than
450 deg.C, open ID fan damper 5%. Due to natural draught created by chimney,
flue gas passes through Boiler and slow heating and expansion takes place.
2. After
opening of ID fan damper, Boiler furnace temperature rises slowly. When the
furnace temperature rises to 250 deg C, Open ID fan damper 10%.
3. When
Flue gas temperature at PCC outlet rises more than 600 deg C., close the ID fan damper and
start ID fan.
4. When
Drum pressure reaches 5 Kg/cm2, close the Drum vent and Puppy header vent.
5. When
Boiler Drum pressure reaches 20 Kg/cm2, give blow down of the water wall to
remove the deposition or sludge.
6. By
adjusting damper opening raise the Boiler pressure upto 45 kg/cm2 and 485 deg
C.
7. Start-up
vent should be in open condition since the admittance of hot flue gas in
boiler.
8. Open
the Main steam line drains in between Boiler Main Steam Stop Valve (MSSV) and
TG MSSV.
9. Open
the MSSV by pass valve to remove all the condensate in main steam line and
ensure that TG MSSV is in close condition.
10. After
removal of all the condensates in Main steam line and proper line heating, open
Main Steam stop valve of Boiler.
11. Close
Super heater drains.
12. Put
Drum level controller in Auto mode.
13. Put
Attemperator controller in Auto mode.
14. Close
Start up vent as per the steam demand of TG set.
15. Charge
ESP when Flue gas temperature after Economizer reaches 160deg. C
Finally the flue gas passes through
Electrostatic Precipitator (ESP) and exhausted to atmosphere through chimney.
At ESP the dust particle in the flue gas is trapped and clean gas escapes to atmosphere.
Ash which is produced in the Boiler due
to combustion of solid fuel is collected at Boiler bottom and also in
Economizer, Air Pre-heater and
ESP.
This ash is disposed off with the help of suitable ash handling system.
Start-up of
Waste Heat Recovery Boiler (WHRB)
Hot Start-up
Hot Start-up
Start-up
of Boiler within 2 Hrs of Tripping of Boiler is known as the Hot Start-up of
Boiler.
1. Ensure
the Drum level of Boiler. It should be at Normal water level.
2. Start
Air Compressors.
3. Start
Boiler Feed water Pump.
4. Start
ID fan with ID damper in Zero position.
5. Open
Start-up vent.
6. Slowly
open damper of ID fan. Watch Drum level.
7. Regulate
Boiler pressure by opening start-up vent.
8. Super
heater temperature has to be maintained with the help of attemperator control
valve.
9. Raise
the Boiler pressure upto 45 Kg/cm2 and temperature to 485 deg C.
10. Open
the drains of Main steam line in between Main Steam Stop Valve (MSSV) of Boiler
and Turbine.
11. Open
By-pass valve of MSSV.
12. Condensate,
if any, will be drained out and main steam line heating will be carried out by
opening of by-pass valve.
13. After
ensuring proper Main steam line heating, open Main
14. steam
stop valve.
15. Close
all drains in main steam line.
16. Charge
ESP when flue gas temperature at Economizer outlet reaches 160 deg C
17. Put
drum level controller and attemperator controller in Auto mode.
18. Regulate
the pressure of Boiler with the help of start-up vent.
19. Close
Start-up vent as per the steam demand of TG set.
20. Normalize
ID fan damper by gradual opening and loading of Boiler.
Charging of
De-areator
It removes the dissolved gases from the
condensate mechanically by
following two laws
1. Henry’s
Law
2.
Dalton’s Law of Partial
Pressure.
·
According to Henry’s
Law, Solubility of dissolved gases decreases by increasing water temperature.
So by charging steam in Deaerator water temperature increases and soluble gases
in condensate departs.
·
According to Dalton’s
Law of Partial Pressure Pm= Ps+Pa
Where
Pm= Partial pressure of Mixture
Ps= Partial pressure of Steam
Pa= Partial pressure of Air
·
The partial pressure of
air present inside the Deaerator comes out
·
through Deaerator vent
for equilibrium state.
Procedure Of Charging
1. Ensure
DM Storage Tank level is more than 60%.
2. Start
DM Transfer Pump by opening Recirculation valve.
3. Ensure
Deaerator level is 60%. If the level is less then take the make up water .
4. Open
all drain lines of Pegging PRDS line and
observe that condensate is completely drained out.
5. Slowly
open Pegging PRDS pressure Control Valve and ensure that condensate is drained
out completely. Then close the drains.
6. Gradually
increase the pressure to 2.8 Kg/cm2 by increasing pegging PRDS pressure control
valve.
7. Slowly
heat the Deaerator by opening the heating line isolation valve and raise the
Deaerator temperature to 90 deg C.
8. Open
the before and after isolation valve of Deaerator Pressure Control valve. Then
open the pressure control valve gradually. Slowly increase the Deaerator
pressure upto 2 kg/cm2 .After that put the Deaerator Pressure control valve in
Auto mode.
9. Start
LP Dosing pump.
10.
In LP Dosing Hydrazine
is used. Hydrazine removes oxygen by chemical reaction.
11. EQUATION-
N2H4+O2=2H2O+N2
12. By adding Hydrazine
dissolved oxygen becomes water and Nitrogen gas releases.
WHRB Interlocks
1. If
Drum level becomes very low i.e. 25% then ID fan Trips and Emergency cap opens
2. This
is to protect the Boiler tubes. At low Drum level, heat flux input has to be
cut off, to protect the Boiler tubes, otherwise starvation takes place.
3. If
PCC out let temperature rises to 1050 deg C then ID fan damper becomes Zero and
Emergency Cap opens.
4. This
protection is incorporatedto protect the Boiler tubes from overheating.
5. If
all BFPs trip then ID fan damper becomes Zero and Emergency cap opens.
6. When
all running BFPs Trip, then Drum level falls drastically. To protect the Boiler
from starvation heat flux input should be cut off.
7. If
Deaerator level becomes very low i.e.25% then All BFPs Trip.
8. Running
of BFPs at Low Deaerator Level is harmful for the Pump.
9. If
Ash Silo level is high, all ash handling systems stop.
10. When ash Silo is at
high level then conveying more ash from ash handling systems results line
blockage of ash conveying line. To prevent this, it is better to stop the
systems and unload ash from Ash Silo.
11. Boiler Main steam stop
valve will not open if by-pass MOV of MSSV is in close condition.
12.
This protection is to
avoid line hammering due to presence of condensate in main steam line and to
prevent carry over of condensate towards Turbine side.
13. Boiler Feed Water MOV
will not open if by-pass MOV of Feed water MOV is in close condition.
14.
If feed water is empty in Economizer and in the
pipe line after Feed water MOV, then by opening Feed water MOV directly without
opening FW by-pass, MOV will lead to overloading of BFP, resulting BFP Trip.
15. ESP trips, if Ash
Hopper level is high.
16.
ESP has high voltage.
Ash has presence of combustibles.
17. This protection is to
safeguard ESP at Ash Hopper level high.
18. ESP can not be charged
without starting of Purge Air Blower.
20. This is to Seal the ESP
by the air from Purge Air Blower before charging it.
22. ESP can not be charged
till flue gas inlet temperature reaches 160 deg C.
23.
This is to avoid
deposition of moisture and oil content influe gas on ESP.
1. Decrease in Drum level
a. Tripping
of Feed Pump
If
Boiler feed Pump trips then Feed water supply to Boiler interrupts and leads to
lowering of Drum level. If this has happened then ensure that the auto stand-by
Boiler feed pump has started in Auto mode. If the auto stand-by Boiler Feed
pump has failed to start in Auto mode then start the Boiler feed pump manually
otherwise Boiler will suffer from starvation and ultimately it will lead to
Boiler trip to protect the Boiler.
b. Tube
failure in Economizer
If Boiler Economizer
tube fails then water supply to Boiler Drum will be affected. This leads to
decrease in drum level and Feed Control valve will open more to compensate the
Drum level to Normal water level, which leads to overloading of Boiler Feed
pump.
Observe
the steam flow and feed water flow. If feed water demand to drum is increasing
then observe any sound from the furnace. If tube has failed inside boiler then
hissing sound comes and it can be noticed from outside. Simultaneously check
the smoke from the chimney. If it is of white colour then tube failure in side
the furnace is confirmed.
c.
Unit getting into Island
mode
When Unit comes to Island mode, it follows the load connected to the
Generator. Suppose Unit is generating
more power than the Unit load and exporting to Grid.
At the time of Islanding,
Generator will follow the load connected in this Unit and the Governing Control
Valves would close according to load and allow the steam to pass through
Turbine. The surplus amount of steam will remain in Boiler which increases the
Drum pressure. This drum pressure will exert a downward thrust to the drum
level and it decreases drastically.
d.
Whether CBD valve, EBD valve
or IBD valve opened?
If
any operating personnel has opened any of these valves without proper reason or
intimation then also drum level decreases rapidly. Ensure first then close the
valve or regulate it observing the drum level.
2. INCREASE IN DRUM LEVEL
a. Whether Cold
start-up in Boiler is in progress?
During Cold start-up when water temperature reaches 900
C then formation of bubble starts. This is known as swelling phenomenon. If
this is the case then blow down has to be given to maintain the drum level at
Normal water level.
b.
Whether
Instrument air compressor tripped and air lock unit at feed control station
failed?
If Instrument air compressor trips, then air lock unit
of control valve at feed control station keeps the control valve at a position
at which it was, before supply of instrument air. This is known as stay put
condition. If air lock unit fails to keep the feed station control valve at
stay put condition, then when supply of instrument air fails, it leads to 100%
opening of control valve. If this happens, start the instrument air compressor
as early as possible and regulate the feed station control valve.
c.
Whether
Start-up vent has opened or safety valve popped up?
By opening
start-up vent, when Boiler is in steaming condition, supply of steam to Turbine
Drum level increases rapidly due to release of pressure in drum. If the steam
demand in TG has reduced to a large extent then it results Boiler drum pressure
rise quickly and at that instant drum level falls rapidly. When start-up vent is operated to release the
surplus steam or safety valve pops up,
then drum level increases rapidly. In this case at first ensure for what
reason the pressure in Boiler has increased. If drum level is increasing
drastically then give blow down to regulate it. Because at higher side drum
level, the steam quality will be affected and carry over of water particles to
super heaters and turbine will take place, which is very much harmful.
d.
Whether
Start-up vent has opened or safety valve popped up? Continued….
Operation
should not be carried out when Boiler is in loaded condition. Donot close the Feed Control valve fully if
drum level rises because if the control valve is closed completely, the feed
water in Economizer tubes, which was passing to Drum, will became steam due to
heat in flue gas and when feed water supply through Economizer will be again
established through Feed control valve then hammering in Economizer tubes due
to presence of steam. This may lead to Economizer tube failure. After ensuring
the reason, close the start-up vent and dump the surplus steam in Condenser.
Ensure that the safety valve has been reset in its position and no passing is
observed.
e. Whether drum level transmitter is malfunctioning?
If drum level
transmitter is malfunctioning then observe the level in hydrastep and
immediately inform shift in charge and instrument personnel about this.
f. Whether rapid heat supply to Boiler?
If heat supply to Boiler will be increased suddenly
with a huge amount then it affects the drum level and it swells. To avoid this
regulate the heat input supply in a gradual loading manner. Sudden and huge
amount of heat supply will overheat the grain structure of the tubes and it
suffers from fatigue. In course of time tube fails.
g. Whether stand-by Boiler Feed Pump has started?
When stand-by Boiler feed water pump has started with
running Boiler feed water pump, then Drum level increases because at that
opening in Boiler feed Control valve when feed water pressure increases, more
feed water flows to drum due to that opening of control valve and leads to
increase in drum level. This case normally happens during scheduled Equipment
change over of Boiler feed water pump. At first the stand-by feed water pump is
started and discharge valve of the respective feed water pump is opened. After that the previously running Boiler feed
pump is stopped. Ensure whether it is a scheduled equipment change over.
h. Whether TG has come to Island mode?
If TG has come to Island mode then Boiler pressure
increases as there is a cut off steam demand as Generator has to follow the
load, connected to it in this unit. If unit was exporting the power to Grid
then the surplus power will be reduced at that instant,
which the Governor of the TG set will follow. It
closes the control valve and steam pressure rises in Boiler accordingly. Ensure
that the unit is running under Island mode. Open the start up vent to release
the pressure. Ensure that the Safety valve has popped up or not. If popped up
then it has reset properly or not. Observe the drum level during this
operation. Observe the Dump control valve is functioning properly or not. If it
is responding properly then try to supply steam to condenser by closing start-up
vent after ensuring that Boiler pressure has reduced and safety valve has
reset.
h. Whether TG
tripped?
If turbine trips then steam demand in Turbine will cut
off and resulting Boiler pressure rise. Ensure Dump circuit is healthy. Open
the Control valve of dump and close the start-up vent after ensuring that the
safety valve reset.
i. Whether any Cooling water pump in TG has tripped?
When Cooling water pump in TG for Condenser condensate
cooling trips then the vacuum in condenser drops quickly and at that instant if
the auto stand-by pump fails to start then the load set point at Generator has
to be reduced with immediate effect. Otherwise the TG will trip due to low
vacuum. When load set point at Generator decreased suddenly then Boiler
pressure increases. In this case communicate with the TG operator and open
start-up vent and lower the Load set point. Try to start the Main cooling water
pump manually. After restoration of cooling water pump divert the steam from
start-up vent by closing it to the dump circuit and normalize the load of
Generator.
3. Decrease in Boiler Steam Pressure
a. Whether
flue gas inlet temperature has reduced?
If
flue gas inlet temperature reduces then it steam generation reduces in Boiler
and pressure drops. This has to be observed very carefully and the generator
Load set point has to be lowered, otherwise the TG will trip when the Main
steam pressure becomes low.
b. Whether more steam demand at
TG end?
If the unit is
running at low load as steam generation in Boiler is low. If as a mal operation
Load set point at Generator is given more than steam generation then Boiler
pressure decreases. and TG is running with low load set point. Unit is
importing power from Grid. If unit came to Island mode then the Generator will
follow the load which is connected to it and load set point at Generator
increases than the steam generation in Boiler. So Boiler pressure decreases. As
we can not change the load set point of Generator by putting lower set point
value, Load on the Generator has to be lowered by cutting off the load
connected to it. Choose the less important load connected to Generator and cut
off it as quickly as possible otherwise the unit will suffer from Black out
condition due to TG trip at Main steam pressure low and Grid power is
unavailable.
The
same case happens when the steam generation in Boiler is low
c. Whether superheater tube
failed?
If superheater tube fails then Boiler steam pressure
decreases. Observe steam flow and feed water flow. If steam flow is at lowering
trend and feed water flow is at increasing trend then it indicates that tube
has failed. If the tube failure has occurred in side the furnace then white
smoke comes out from chimney. When steam pressure decreases then reduce the
Generator set point accordingly to avoid TG trip at main steam pressure low and
ensure whether tube has failed or not. If tube has failed then Boiler shut down
has to be taken to replace the failed tube with a new tube.
d. Whether ID fan damper has closed to zero
position?
This case happens when flue gas temperature at Post
Combustion Chamber reaches 10500 C. Flue gas flow to Boiler cut off
when ID damper closes. It means heat supply to Boiler has cut off. It results
in less steam generation. So when ID damper closes due to high PCC temperature,
immediate load reduction has to be carried out in Generator to avoid TG trip
due to Main steam pressure low.
e. Whether hand lever of Safety
valve has been operated?
If any person has operated the hand lever of safety
valve without proper communication with the operating personnel for sometime
then Boiler steam pressure decreases and drum level increases.
4. INCREASE IN MAIN STEAM TEMPERATURE
a. Whether Boiler is loaded
with huge amount of heat suddenly?
Main steam temperature rises if flue gas temperature
at Boiler inlet rises suddenly. As superheaters are located at convection
zone, therefore when flue gas
temperature rises, it increases the superheater temperature. If attemperator
control valve fails to control the main steam temperature then TG will trip due
to main steam temperature going high. In order to avoid such a situation, if
main steam temperature rises due to rise in flue gas temperature, then
immediately attemperator control valve has to be taken to manual mode and
attemperation should be increased. Also communicate with the kiln personnel
about the sudden rise in flue gas temperature.
b. Whether Soot Blowing is in
progress?
During soot blowing, steam temperature rises because
more steam is required for soot blowing and heat input to the Boiler has been
increased by opening the ID fan damper. So during soot blowing, main steam
temperature has to be observed carefully.
If attemperator control valve fails to control the rise in main steam
temperature in auto mode, then it has to be controlled taking it to manual
mode.
c. Whether Attemperation
control valve is in manual mode or wrong value command input by the operator?
Normally it happens when there is a high fluctuation
in main steam temperature. The attemperation control valve fails to control the
temperature in Auto mode. So the concerned operator has to take the
attemperation control valve to manual mode to control the temperature. But if
he forgets to put this control valve in Auto mode after stabilization of main
steam temperature, then it will remain in manual mode and during more heat input from Kiln, the main steam
temperature would rise. Also sometimes operator puts wrong value command for
attemperation control valve opening from control station in manual mode, which
would result in increase in main steam
temperature.
d. Whether forget to open
before and after isolation valves of attemperation Control valve?
This situation comes during cold start-up of Boiler,
if the inspection and checking was not done properly by the operation
personnel. During initial period, this thing cannot be noticed but at the time
of main steam temperature rise by opening attemperation control valve flow of
water cannot be established as before and after isolation valves are in close
condition. So care has to be taken for proper inspection and checking before
start-up.
5. DECREASE IN MAIN STEAM TEMPERATURE
a. Whether inlet flue gas
temperature has dropped?
If flue gas inlet temperature drops due to problem in
Kiln side then main steam temperature decreases. So if main steam temperature
is in decreasing trend then first observe the flue gas inlet temperature to
Boiler.
b. Whether Load set point is
given in Generator more than the Steam generation?
If Load set point in Generator is given more than the
steam generation in Boiler then main steam pressure decreases and also the main
steam temperature decreases
c. Whether valve sheet of
Attemperation control valve is eroded?
This situation comes during Low Load operation of
Boiler. If heat input to Boiler is low, then steam generation reduces and also
the power generation. At that time, feed water passes due to eroded valve sheet
of attemperation control valve and decreases main steam temperature.
d. Whether ID damper has become
Zero due to PCC outlet temperature High?
When Post Combustion Chamber temperature increases
more than 10500C, opening of ID damper becomes Zero. At that time
heat supply to Boiler from Kiln stops suddenly. So it results in rapid decrease
in main steam temperature. If this situation arrives, then attemperation
control valve has to be taken to Manual mode from Auto mode and decreasing main
steam temperature has to be controlled.
6.
FURNACE
DRAUGHT TOWARDS POSITIVE SIDE
a. Whether tube failure has
occurred in side furnace?
In furnace, the draught is maintained at negative side
to carry out the hot flue gas, ash and other suspended particles from kiln to
chimney through ID fan. If Boiler tube fails inside furnace then draught goes
towards positive side. As steam density is higher than air density. Also it adds an additional load on ID fan. So
ID fan takes more current in this situation.
b. Whether draught transmitter is showing wrong
value?
This can be known if other draught transmitters in
flue gas path are showing right value and one of these is showing erratic
value. This problem should be brought to the notice to shift in charge and
instrumentation personnel.
7. LONG RETRACTABLE SOOT BLOWER IS NOT AT ITS
ORIGINAL POSITION
a. Whether Long Retractable
soot blower’s chain has broken during Soot Blowing operation?
If chain breaks at intermediate position of lancer
tube during soot blowing by LRSB, then motor will be unable to retract it to
the original position i.e. home position. Check the position of lancer tube,
when soot blowing operation is in progress and chain has broken. In this
situation, donot cut off steam flow through lancer tube. It is because it is
situated in high heat zone i.e. at convection zone. As steam acts as a coolant,
it will take the heat added to the lancer tube and will protect the lancer tube
from over heating and bending. The lancer tube has to be drawn out manually.
After ensuring that it has been drawn to its home position, steam through the
lancer tube can be cut off and chain maintenance work can be carried out.
b. Whether home position limit
switch is malfunctioning?
This may happen after completion of soot blowing by
Long Retractable Soot Blower. The limit switch at home position may not give
home position feed back of the LRSB due to malfunction. If this case happens
then immediately the position of the lancer tube has to be checked. Limit
switch at home position has to be rectified by Instrumentation department.
c. HAMMERING OF MAIN STEAM LINE DURING
CHARGING.
Usually main steam line hammering occurs if the
condensate present in that line is not properly drained out and pipe line is in
cold condition. If huge amount of steam is allowed to pass through that pipe
line then line hammering takes place which is very much harmful for the pipe
line. So to avoid this case happening always open the drain of the pipe line.
Observe the condensate is drained properly from that pipe line. After
completion of condensate draining, warm-up the pipe line with very less
quantity of steam. Gradually increase the pipe line temperature. After
confirmation that the line is properly heated, more steam flow can be allowed.
Steam Turbine
Steam turbine is a mechanical device that extracts
thermal energy from steam and converts it into mechanical work. Interiors of a turbine consists of several
sets of blades. Some set of blades are fixed at casing ( Fixed Blade) and some
set of blades are fixed on the rotor ( Moving Blade) .
Fixed blades convert potential energy of the steam
into kinetic energy and direct the flow to moving blades. Moving blades convert
this kinetic energy in to force, caused by pressure drop and result in rotation
of turbine shaft. Steam is allowed to enter into the turbine through control
valve. This steam after passing through different stages of blades is allowed
to exhaust. The exhaust steam is condensed in a condenser and condensate then
reused in boiler.
1. Impulse Turbine
2. Reaction Turbine
1) IMPULSE TURBINE:
In Impulse turbine instead of set fixed blades a set
of nozzles are fitted in the casing. Pressure drop of steam takes place in
these nozzles and velocity of steam increases. This high velocity jet of steam
contains significant amount of kinetic energy. This high velocity steam is
passed through a set of moving blades, where pressure of the steam remains
constant and velocity decreases.
2)
REACTION TURBINE:
In reaction turbine fixed blades are fixed in the casing.
Shape of these blades is such that the space between the blades has cross
section same as shape of nozzle. Moving blades are fixed to the rotor. Fixed
blades guide the steam to moving blades . Blade shape is so designed that steam
glides over the blades. Steam while gliding over moving blades produces
reaction on the blade. This reaction force produce the rotates the rotor.
1.
Casing
2.
Rotor
3.
Moving Blade
4.
Fixed Blade
5.
Steam Sealing
System
6.
Bearing
Ø Joural Bearing
Ø Thrust Bearing
7. Gland
8. Exhaust Hood
9. Emergency Stop Valve
10.
Governing Valve
And Control Valve
11. Barring Devices.
12. Governing
Systems
v CASING
Casing of turbine plays important role for the
performance of a turbine. This is the outer shell of turbine. Fixed blades and
nozzles are attached to this. Casing facilitates to accommodate moving parts
and provides passage for steam. Normally it is formed by casting. As the
temperature of steam for operating turbine is high so, normally Cr, Mo alloy
steel casting is used for casing of a turbine. Metal to metal joint sealing is
done to ensure no leakage of steam.
v ROTOR
Rotor is the moving part of a turbine which extracts
work from steam. This is the heaviest part of the turbine. Normally total shaft
is manufactured by forging. Rotor consist of shaft moving blade and inter stage
sealing labyrinth. Thrust collar is provided to take care of axial thrust of
rotor during various load conditions. Rotor of the turbine is allowed to expand
uniformly. Rotor of the turbine should not be allowed to remain stand still
when it is hot. Due to its self weight there is a chance of sagging or
deformation. Rotor
v Moving Blades
Enthalpy of steam is converted into rotational energy
as it passes through turbine blade sets. In each stage of the turbine there are
moving and fixed blade. As in each step pressure of steam decreases, its volume
increases. The blade has to handle more volume of steam. Blade has to withstand
high pressure and temperature of steam.
Good tensile and fatigue strength is required. Good vibration damping property,
low ductility, resistance to corrosion and erosion is essential. Blade can be
divided into three portions.
1. Tip
2. Profile
3.
Root
v Fixed Blades
Fixed blades facilitate expansion of steam and guide
it to flow over subsequent moving blade row. Partition between pressure stages
in a turbine casing are called diaphragms. It holds vane shaped nozzles or
fixed it
MAIN
COMPONENTS OF STEAM TURBINE
1.
JOURNAL
BEARING
Journal bearing is a cylinder, which surrounds the
shaft and is filled with some form of fluid lubricant. It consists of a split
outer shell of hard metal and soft metal at the inner cylindrical part. In this
bearing a shaft or journal rotates inside the bearing over a layer of
lubricating oil, separating the shaft and bearing through a fluid film by
dynamic principle. Inner surface of this bearing is coated with a soft metal
called as white metal or Babbitt. This is a tin or lead based alloy.
2.
THRUST BEARING
Journal bearings are used to
take radial load of the shaft. But it can’t take axial load. Shaft is permitted
to float to both axial direction. But the axial float is restricted to certain
limit. Excessive axial shift may damage rotating and fixed parts. For this
thrust bearing is provided.
EMERGENCY STOP VALVE
Ø This valve is normally hydraulically operated. The
valve opens hydraulically against a spring force. To close the valve
hydraulically
Ø Fluid is drained and valve closes immediately due to
force of spring. This valve is normally fully open and fully close type.
Auxiliary System Of Steam Turbine
1. OIL SYSTEM
Ø Oil tank
Ø Oil Pump
Ø Oil Cooler
Ø Oil Filter
Ø Oil Centrifuge
Ø Oil Over Head Tank
Ø Accumulator
2.
CONDENSATE
SYSTEM
3.
GLAND
SEALING SYSTEM
4.
STEAM
EJECTOR AND VACCUM SYSTEM
5.
CONDENSER
6.
COOLING
WATER SYSTEM
Turbine Cold Startup Sequence Method
Operation of steam turbine is a complex process.
Before starting the rolling of a turbine, auxiliary systems are to be properly
put in service. Normally for start up of a turbine some operations are followed
in sequence.
v Charging of Steam Pipe Line
From Boiler,
steam is carried to turbine main steam pipe line. In cold condition, special
care is to be taken to heat up the steam line and allow gradual thermal
expansion, before giving full load on the turbine.
Drain points are provided at the steam line to drain
out condensate present in steam pipe line, that is formed due to condensation
of steam. First of all, these drains are opened before charging steam on the
pipe line. After condensate is drained out boiler main steam stop by pass valve
is opened slowly .
Some steam is allowed to flow through the pipe line
and it starts gaining heat from the steam and steam is condensed. At the
beginning, condensate along with some steam is allowed to come out through the drain.
These drains are throttled slowly and closed when no more condensate but only
dry steam comes out from the drain.
Steam traps provided in the pipe line are kept in line
once drains are closed. Then Main Steam Stop Valve of the boiler is opened slowly
so that the line temperature is increased gradually. Ensure extraction is not
restricted anywhere. Watch the temperature of bypass reaching the normal level
after which stop valve of boiler can be opened fully.
To circulate cooling water in the Condenser, cooling
water pumps are to be started.
Before
starting pump
1.
Ensure Sump
level of the cooling tower basin is normal (>80%)
2.
Keep suction
valve of the pump in open condition & discharge in closed condition.
3.
Ensure inlet
& outlet cooling water valves of Condenser distributer valves of cooling
tower are in open condition .
4.
Ensure vents
provided at Condenser water box are in open condition to remove trapped air.
5.
Start the pump
& open the discharge valve .
6.
Observe whether
cooling water is falling on the cooling tower or not.
7.
Ensure that
distribution of cooling water in all chambers is equal, otherwise adjust the
valves provided at the distribution header .
8.
Observe whether
all the cooling water pumps are sharing load or not.
9.
Once Turbine is
started and loaded, cooling tower fans can be started one by one as per
requirement.
Starting Of M.O.P ( Main Oil Pump )
1.
Before starting
of M.O.P check the healthy condition of
Main Oil Tank ( M.O.T ) low level switch from H.M.I .
2. Before starting
M.O.P, check oil level in M.O.P oil cup
as well as oil level in A.O.P & E.O.P oil cups.
3.
Ensure again
suction & discharge valves of M.O.P, A.O.P & E.O.P are in open
condition .
4.
Start M.O.P .
5.
Open J.O.P
suction line coming from M.O.P &
A.O.P discharge header , then open its discharge valve .
6.
Put A.O.P, J.O.P
& E.O.P in auto selection mode.
Taking Oil Cooler into Line
1.
When M.O.P
starts, oil circulates to the circuit through oil cooler
2. To ensure oil is
passing through the oil cooler or not, see through the view glass after opening
the air vent of oil cooler
3. After confirming
oil is passing through the vent valve to M.O.T, close the vent valve
4.
Open the oil
equalizing line of standby oil cooler and wait for some time to fill it with
oil, then close the equalizing valve
5. Maintain lub oil
temperature in between 420C - 450C by adjusting the
outlet cooling water valve of online
cooler
Taking Oil Cooler into Line
1.
When M.O.P
starts, oil circulates to the circuit through oil cooler
2. To ensure oil is
passing through the oil cooler or not, see through the view glass after opening
the air vent of oil cooler
3.
After confirming
oil is passing through the vent valve to M.O.T, close the vent valve
4.
Open the oil
equalizing line of standby oil cooler and wait for some time to fill it with
oil, then close the equalizing valve
5.
Maintain lub oil
temperature in between 420C - 450C by adjusting the
outlet cooling water valve of online
cooler
Checking Of Lub
Oil Header Pressure and Individual Bearing Pressure
1. Check the lub.
oil header pressure from field and H.M.I . It must be more than 3Kg/cm2.
2.
Check the
individual bearing oil pressure
i.
TG Front Journal
Bearing – 1.2 Kg/cm2
ii.
TG Thrust
Bearing – 1.2 Kg/cm2
iii.
TG Rear Journal
Bearing – 1.2 Kg/cm2
iv.
Gear Box – 2
Kg/cm2
v.
Alternator Front
Journal Bearing – 1 Kg/cm2
vi.
Alternator Rear
Journal Bearing – 1 Kg/cm2
3. Check
individual bearing's return oil line view glass whether oil is
passing through it or not.
4. Check overhead
tank oil return line view glass , ensure oil flow through return oil line then
close quick filling valve of overhead tank .
5.
Check
healthiness of overhead tank oil level indicator .
Once the above systems
are in service, gland steam can be charged at gland. Care is to be taken
while charging gland steam in a cold Turbine. As the gland area of Turbine is
at normal temperature during cold condition, hot gland steam may produce
thermal shock at that area. To avoid this, steam is to be charged slowly and
condensate produced is to be drained through gland steam drain.
Following steps
are to be followed for gland steam charging :
1.
Charging of
auxiliary PRDS (Pressure Reducing & De Superheating)
2.
Charging of
Gland Header
3.
Charging Of Aux PRDS (Pressure Reducing And De-Superheating)
4.
Open all drain
valves
5.
Open main manual
isolation valve before & after PCV
(Pressure Control Valve)
6.
Open PCV by 5%
from operation station
7.
Open PCV by 10%
as soon as condensate comes out from line
8.
Close all drain
valves
9.
Put the PCV in
Auto mode with desired pressure set point
10.
Open manual
isolation valve of TCV ( Temperature
Control Valve)
11.
Observe the
temperature and then put TCV in auto mode with desired temperature set point
Charging of Gland Header
1.
Open all drain
valves of gland steam header
2.
Open gland steam
header manual isolation valve
3.
Open gland steam
header PCV by 5% for line heating.
4.
Open gland steam
header PCV by 10% to increase gland steam header pressure
5.
Close all drain
valve in gland steam header
6.
Put gland steam header PCV in auto mode with desired pressure set point.
Exhaust steam of turbine is condensed at condenser
with the help of cooling water. The condensate produced is evacuated from the
condenser by the help of Condensate Extraction Pump (CEP). This condensate
passes through gland seal condenser and ejector condenser to gain heat of the
gland steam and ejector steam respectively. So the temperature of condensate
increases there before feeding to deaerator for further use at boiler.
This condensate is further heated at L.P. Heater (if provided) by using LP Steam extraction of
turbine.
To put the condensate system in operation, following
steps are required to be followed:
1. Ensure condenser
hot well level is adequate, otherwise fill the hot well with make up DM Water
2. Open Suction and
discharge valves of the pump. Ensure differential pressure of the strainer is
normal
3.
Open condensate
inlet and outlet valves of gland seal condenser, ejector condenser and LP Heater
4.
Put the
re-circulation control valve in auto mode
5.
Open pump gland
cooling valve and start the pump
The condensate will pass
through gland seal condenser & ejector condenser. It should be re circulated to condenser again
through recirculation control valve.
Once steam starts entering into turbine, discharge control valve can be put in
auto mode to maintain level of the hot well.
If the condensate extraction pump is to be started and if there is
vacuum inside the condenser, then vacuum balance line valve is to be opened to
avoid any air trapped inside the pump.
Before Main steam enters
into the turbine, there should be vacuum in the condenser. First of all,
starting ejector is used to evacuate air from condenser. This is a single stage
non-condensing type ejector.
Take
the following steps to build up vacuum
by starting ejector:
1.
Ensure
availability of auxiliary steam at desired pressure & temperature
2.
Ensure the
vacuum breaker valve of the condenser is closed.
3. Ensure cooling
water is circulating in the condenser and turbine gland is charged fully
4.
Open steam valve
of the starting ejector
5.
Observe steam is
vented to atmosphere
6.
Open ejector air
valve
7.
Observe vacuum
inside condenser is increasing slowly.
8. Main ejector is
to be taken into line once turbine is loaded and starting ejector is to be stopped then.
To put main ejector into
line, following steps to be followed :
Main
ejector is to be taken into line once turbine is loaded. Starting ejector is to be stopped then. To
put main ejector in line, following steps to be followed.
1.
Ensure
Condensate Extraction Pump (CEP) is running .
2.
Ensure cooling
water inlet and outlet valves of the ejector condenser are opened.
3. Vent out air
from water box of the ejector condenser
by opening rotametre valve.
4.
Open ejector
condensate trap before and after isolation valve
5.
Fill up the “U”
tube by water locally
6.
Open flash box
stand pipe isolation valve
7.
Close all drain
valves of ejector
8.
Open the main
isolation valve of the ejector steam line
9.
Slowly open the
air line valve of the ejector and observe vacuum is increasing.
When vacuum is
stable, then the slowly ejector can be stopped by closing air valve first
then the steam valve of ejector.
Once Auxiliary systems are in operation and full
vacuum is obtained inside, condenser turbine can be started. Turbine is
required to be started in two different conditions.
1.
Cold Start-Up
2.
Hot Start-Up
In cold startup
turbine is started from cold condition. In this case, special care is taken for
proper heating of casing and rotor for proper thermal expansion. As both rotor
and casing are in cold condition it requires time for heat up. But in case of
hot start up both casing and rotor are in hot condition. So it can be started
within a short period.
Startup Curve
To allow proper thermal explanation of casing and
rotor, the turbine manufacturer’s advise is to be followed for start up
procedure.
Ø steam should not enter immediately to turbine as it
may damage the turbine due to uneven expansion.
Ø Manufacturers suggest soaking time for low idle speed
and high idle speed for proper thermal expansion between rotor and casing means to hold the turbine at the
particular speed for a particular time, then allow the turbine speed to higher
range.
Soaking time is different for cold startup and hot
startup. Manufacturer’s advice should
always be followed strictly for soaking and start up curve in cold startup and
hot start up conditions.
Turbine
Rolling Preparation..contd
To start rolling of turbine, some steps are followed
depending upon mode of starting (Auto or Manual) and types of governing
system (Hydraulic or Electro Hydraulic)
Before rolling
of turbine check, ensure the following points :
1.
Lube oil level
and control oil pressure are normal
2.
Lube oil
temperature is between 42 to 450C
3.
Ensure gland
sealing system is in operation and gland sealing pressure is normal
4.
Ensure starting
ejector is in the line and condenser pressure is -0.9 kg/cm2
5.
Ensure cooling
water is circulating in condenser and auxiliary cooling water in lub. oil cooler
6.
Ensure the
casing drain, TG inlet steam line drain, TG warm
7. up vent and drain are in open condition
8.
Ensure
Accumulator is in line
9.
Ensure over head
oil tank is full and return oil flow is visible in the viewing glass
10.
Ensure
Condensate Extraction pump (CEP) is in operation
11. Ensure
Exhaust hood spray solenoid valve is in
operating condition.
12. Open the bypass
of Turbine Steam stop valve (TSSV)
13. Ensure complete
removal of condensate from TG inlet line and ensure the temperature of TG inlet
steam is rising after throttling drain valves.
Open Turbine Steam Stop Valve
(TSSV)
14. Throttle the
warm up vent as per requirement and observe steam temperature is rising. Once
steam temperature reaches at desired temperature, then prepare for TG rolling.]
TG Rolling
1.
Reset the
governor from wood yard SOS
2.
Reset from HMI
3.
Engage trip
lever and ensure build up of trip oil pressure at governing console
4.
Open E.S.V.
(Emergency Stop Valve) from H.M.I.
5.
Check physically
the opening of ESV (Emergency Stop Valve)
6.
Give run command from HMI
7. Observe the rise
in rpm gradually. RPM goes up and after
reaching 1000 rpm (Low Idle speed) automatically, it will hold for 15 minutes
in hot start up and 30 minutes in cold startup (in case of auto rolling). Otherwise hold the speed as advised by the
manufacturer.
8.
Ensure oil
pressure is normal. Check vibration and any abnormal sound
9.
First stop
barring gear then stop jack oil pump
(J.O.P)
10. Get the relay
reset before 2000 rpm
11.
After completion
of the hold time at 1000 rpm, R.P.M. goes from low idle speed to high idle
speed 2500 rpm, if it is in auto mode, otherwise increase the speed manually
12.
After reaching
2500 rpm, it holds for 15 minutes in case of hot startup and 30 minutes in case
of cold startup automatically. If it is not auto rolling, hold the speed as per
advice of manufacturer.
13. Close the TG
casing drain, inlet steam line drain, warm up vent, warm up drain
14.Check the lube
oil pressure at different bearings and check bearing temperature and vibration
and record it.
15.
After completion
of high idle speed (2500 rpm) soaking time. R.P.M. will rise up to rated speed
7500 rpm
16.Maintain lube
oil pressure and temperature at different bearings as per the manufacturer’s
advice
17.
Maintain TG
inlet pressure and temperature as per design
18. Give clearance
to synchronize to generate power.
Turbine Protection Logic
NO
|
DESCRIPTION
|
SET POINT
|
TIME DILAY (sec)
|
1
|
Lube Oil header press lo lo
|
1.2 Kg/cm2
|
2
|
2
|
Lube Oil Press after filter lo lo
|
4 Kg/cm2
|
2
|
3
|
Oil Press lo - Trip device outlet
|
4 Kg/cm2
|
2
|
4
|
Turbine exhaust steam press hi hi
|
-0.6 Kg/cm2
|
2
|
5
|
Cond. Level hi hi
|
95%
|
2
|
6
|
Cond. Level lo lo
|
15%
|
2
|
7
|
Turbine overspeed
|
8220
|
2
|
8
|
Trip command from governor
|
-
|
2
|
9
|
Rotor axial displacement hi hi
|
+/- 0.45 mm
|
2
|
10
|
Turbine front brg vib hi
hi
|
200 micron
|
2
|
11
|
Turbine rear brg vib hi hi
|
200 micron
|
2
|
12
|
GB pinion DE brg vib hi hi
|
200 micron
|
2
|
13
|
GB pinion NDE brg vib hi hi
|
200 micron
|
2
|
14
|
GB G shaft NDE vib hi hi
|
160 micron
|
2
|
15
|
GB G shaft DE vib hi hi
|
180 micron
|
2
|
16
|
Alternator front brg vib hi hi
|
160 micron
|
2
|
17
|
Alternator Rear brg vib hi hi
|
160 micron
|
2
|
18
|
86T relay operated
|
2
|
|
19
|
Inlet steam temp lo lo
|
400/440 deg C
|
6
|
20
|
Inlet steam temp hi hi
|
525 deg C
|
6
|
21
|
Turbine exhaust steam press hi hi
|
-0.6 Kg/cm2
|
0
|
22
|
Turbine NWS thrust brg temp hi hi
|
115 deg C
|
8
|
23
|
Turbine WS thrust brg temp hi hi
|
115 deg C
|
8
|
24
|
Turbine front brg temp hi
hi
|
115 deg C
|
8
|
25
|
Turbine rear brg temp hi
hi
|
115 deg C
|
4
|
26
|
MOP side thrust pad temp hi hi
|
115 deg C
|
4
|
27
|
HS Working Side temp hi hi
|
115 deg C
|
4
|
28
|
HS Non Working Side temp hi hi
|
115 deg C
|
4
|
29
|
Alt. side brg temp hi hi
|
115 deg C
|
4
|
30
|
MOP side brg temp hi hi
|
115 deg C
|
4
|
31
|
HS NWS brg temp hi hi
|
115 deg C
|
4
|
32
|
Drive end brg temp hi hi
|
80 deg C
|
4
|
33
|
NDE brg temp hi hi
|
80 deg C
|
0
|
34
|
Inlet steam press lo lo
|
38/39 Kg/cm2
|
3
|
35
|
Inlet steam press hi hi
|
48/50 Kg/cm2
|
8
|
NO
|
DESCRIPTION
|
SET POINT
|
TIME DILAY (sec)
|
1
|
Lube Oil Press lo
|
1 Kg/cm2
|
|
2
|
Control oil press lo
|
4.5 Kg/cm2
|
3
|
3
|
Trip Oil Press lo (PSLL-305A)
|
2 Kg/cm2
|
10
|
4
|
Exhaust steam press hi
|
-0.4 Kg/cm2
|
|
5
|
Hotwell level hi hi
|
||
6
|
Turb speed hi hi - WWG
|
7865
|
|
7
|
Trip command from governor
|
||
8
|
Turb Axial shaft displacement hi hi
|
+/- 0.7 mm
|
|
9
|
Turb shaft front vib hi hi
|
156 microns
|
|
10
|
Turb shaft rear vib hi hi
|
156 microns
|
|
11
|
Turb shaft front vib hi hi
|
156 microns
|
|
12
|
GB LS shaft rear vib hi hi
|
340 microns
|
|
13
|
GB HS shaft front vib hi hi
|
340 microns
|
|
14
|
GB LS shaft rear vib hi hi
|
340 microns
|
|
15
|
Gen L/O relay 86B operated
|
||
16
|
Inlet steam temp lo
|
400 deg C
|
2
|
17
|
Inlet steam temp hi
|
520 deg C
|
2
|
18
|
Bearing temp hi
|
115 deg C
|
|
19
|
Thrust Brg. Temp 1
|
115 deg C
|
|
20
|
Thrust Brg. Temp 2
|
115 deg C
|
|
21
|
Thrust Brg. Temp 3
|
115 deg C
|
|
22
|
Thrust Brg. Temp 4
|
115 deg C
|
|
23
|
Tur. Front brg
|
115 deg C
|
|
24
|
Tur rear brg
|
115 deg C
|
|
25
|
GB front (HSS) brg Temp 1
|
115 deg C
|
|
26
|
GB front (HSS) brg Temp 2
|
115 deg C
|
|
27
|
GB thrust brg temp 1
|
115 deg C
|
|
28
|
GB thrust brg temp 2
|
115 deg C
|
|
29
|
GB rear (LSS) brg temp 1
|
115 deg C
|
|
30
|
GB rear (LSS) brg temp 2
|
115 deg C
|
|
31
|
Gen front brg
|
115 deg C
|
|
32
|
Gen rear brg
|
115 deg C
|
|
33
|
Inlet steam press lo
|
40 Kg/cm2
|
2
|
34
|
Inlet steam press hi
|
50 Kg/cm2
|
6
|
35
|
Exhaust temp hi
|
120 deg C
|
|
36
|
Turb speed hi hi - TSI
|
7860
|
|
37
|
Emergency trip PB1
|
||
38
|
Emergency trip PB2
|
||
39
|
Turbine trip from HMI
|
Turbine Auxiliary System
In Power Plant other than turbine, there are other
associated systems. The systems are required for running of a turbine. Most of
the important components and systems for
auxiliary systems are :
1.
Oil System
2.
Condensate
System
3.
Gland sealing
System
4.
Ejector and
Vacuum System
5.
Cooling water
System
6.
Condenser
Oil System
Lubricating oil is supplied to the bearings and used
for governing of turbine. Main function of lubricating oil is to :
1.
Lubricate the
bearings.
2.
Cooling of
bearings.
3.
Flush out
metallic debris.
4.
Control speed of
the turbine. \
Principles
of Lubrication
To maintain a film of lubricant between
the surfaces in running condition any one of the following principle of
lubrication prevails.
1.
Hydro dynamic
lubrication
2.
Hydrostatic lubrication
3.
Elasto-hydrodynamic
lubrication
If
none of the above conditions exists the condition will be of :-
Boundary lubrication
Hydrodynamic
Lubrication
Also called Full Flood Lubrication/Wedge film
lubrication
Wedge film formation due to
geometry & speed.
a. In hydrodynamic principle fluid viscosity is not
sufficient to maintain a film between the moving surfaces & higher pressure
required to support the load until the fluid film is established, the required
pressure generated internally by dynamic action.
b. The wedge film lifts the journal and allows complete
separation
c. The formation
of a thick fluid film that will separate two surfaces and support a load
as the two surfaces move with respect to each other.
By feeding oil from an external source under heavy
pressure into the pocket machined into the bottom of the bearings, the journal
can be lifted and floated on fluid films.
When the journal reaches a speed sufficient to create
hydrodynamic films the external pressure can be turned off and the bearing will
continue to operate in hydrodynamic manner.
Components
of Lubricating Oil System
Main components of lubricating oil system are :
1. Oil tank
2. Oil pumps
3. Oil filter
4. Oil centrifuge
5. Oil overhead
tank
6. Accumulators
Oil
tank
Total oil for the system is stored in the this tank.
The tank has adequate capacity to hold sufficient oil during running & stop
condition. The tank base is made sloped to one side, so that the sediment in
oil can be collected in the lower area
and can be drained out by opening drain valve. The tank has level measurement
facility to give alarm for low oil level. Also a level glass is provided to
find out tank level at any instant. Suitable tapings are provided to facilitate
oil suction for oil pumps, draining of return oil from bearings and governing
system, connection for oil centrifuge, fill up of fresh oil etc.
One oil mist fan is provided on the tank to vent out
any oil vapor and keep the tank slightly below atmospheric pressure.
Oil
Pump
To pump oil from the oil tank to various lubrication
points and controlling purpose, oil
pumps are provided. Normally three pumps are provided. These pumps are :
1.
Main oil pump ( M.O.P )
2.
Auxiliary oil pump ( A.O.P )
3.
Emergency oil pump ( M.O.P )
Oil Coolers
Normally
two oil coolers of 100% capacity are provided to cool down entire oil supplied
to turbine bearings,gearbox,and generator bearings for lubrication. Governing
oil is not cooled at oil cooler. This oil taken out before oil cooler. One
cooler is put on line and another one is kept as standby. Online changeover
facility is provided to take the standby cooler in to service, without
interruption of oil supply, while turbine is running.
Before
changeover, it is to be ensured that the standby cooler is filled with oil and
air is vented out properly. Otherwise there will be air lock and oil supply to
bearings may interrupt.
Oil
cooler is a shell and tube type heat exchanger. Cooling water flows inside the
tube bundle and oil flows at the shell side. Cooling water for oil cooler is
obtained from main cooling water system of power plant. Regulating valves are
provided at the inlet and outlet of the cooling water supply line.
To increase and decrease oil temperature, cooling
water flow is decreased and increased respectively through these regulating
valves. Always the cooling water outlet valve is regulated to vary flow of
cooling water. At any case cooling water inlet valve is not to be throttled as
sufficient cooling water will not available inside tub and tube may damage.
Drain point is provided at the cooler to drain out
settled sediment at bottom of the cooler.
Oil
Filters
Oil coming out from cooler is passed through oil
filter to remove any contaminated particle or debris. Filter is normally basket
type with removable filter cartridge. Like cooler there are two filters of 100%
capacity each with suitable online changeover arrangement. The oil is filtered
up to 20-25 micron level on these filters before circulating in bearings.
Differential pressure across the filter is measured
which indicates the choking condition of filter cartridge. If differential
pressure is high it indicates, filter is choked and needs cleaning.
Before changeover of oil filter when turbine is in
operation, it is to be ensured that standby filter is completely filled and no
air is trapped inside. Filter cartridge of standby filter is always to be kept
clean, so that at any moment this can be taken in to line, if required.
Oil
Centrifuge..contd.
Centrifuge is a machine which separates water and
solid particles from oil. This is achieved by centrifugal force of a high speed
rotating bowl inside the separator. Due to centrifugal force, heavier particles
are displaced towards the outer periphery of the bowl and the lighter oil is
displaced towards center of the bowl, where it is collected and sent back to
main oil tank.
Steam Ejector And
Vacuum System
Vacuum is maintained by continuously evacuating non
condensing gases from the condenser with the help of steam ejector. Pressure of non condensing
gases decrease condenser efficiency. For removing non condensing gas to create
vacuum in the condenser normally steam
ejector is used. This is like a pump in which venturi effect of a converging
and diverging nozzle is used to convert
pressure energy of steam to velocity energy to create suction effect.
WORKING PRINCIPLE OF EJECTOR
High
pressure motive steam enters to ejector chest through nozzle and then expanded.
Pressure energy of steam is converted into velocity. Increased velocity causes
reduced pressure which socks vapour.Diffuser section then compress
the steam vapour mixture then exhausted to condenser.
Operating Procedure Of Ejector System
1.
Circulate
condensate through ejector condenser.
2. Open steam of
ejector. So it will create vacuum in inter ejector condenser.
3.
Open steam of
ejector.
4.
Open air valve
of condenser.
Condenser
Condenser
is an important Auxiliary equipment of any steam turbine. Exhaust steam of
turbine is exhausted in to condenser, where it is condensed in vacuum. By
maintaining vacuum in condenser, maximum energy can be extracted from steam and
turbine efficiency increases. Condensate obtained is utilized again at boiler
for steam formation.
There
are different types of condenser. Some of the important types of condensers are listed below.
1.
Jet type condenser
2.
Air condenser
3.
Surface condenser
Surface Condenser
This type of condenser is widely used at power plants.
Cooling water is not mixed with condensate in this case. Condensate obtained is
pure and can be used in boiler. This is a shell type and tube type heat
exchanger. Shell of the condenser is closed. Tubes are arranged inside the
shell in which cooling water flows. Condenser neck is connected to the exhaust
hood of turbine. An expansion joint is provided in-between to facilitate
thermal expansion.
Steam from turbine flows at the shell side of
condenser and cooling water flows inside the tube. Main components of a surface
condenser are :
- Shell -
Hot well
- Air outlet - Tube
- Rapture disk -
Water box
Overhead Tank
Oil
accumulator is provided on the governing or control oil line of the turbine. This
accumulator maintains oil pressure in the line during momentary fluctuation of
oil pressure during oil pump change over or sudden operation of servomotor of
governing valve.
In
the accumulator an inert gas filled bladder is provided. Gas pressure inside
the bladder is maintained slightly below the normal oil pressure.
During
normal operation, oil pressure of the line compress the bladder and oil is
occupied in the oil space of the accumulator. When, pressure at the line drops,
the bladder is expanded, due to the inside gas pressure. So it pushes out oil
of space to the line and takes care momentary oil pressure fluctuation.
Oil Accumulator
Oil
accumulator is provided on the governing or control oil line of the turbine.
This accumulator maintains oil pressure in the line during momentary
fluctuation of oil pressure during oil pump change over or sudden operation of
servomotor of governing valve.
In
the accumulator an inert gas filled bladder is provided. Gas pressure inside
the bladder is maintained slightly below the normal oil pressure.
During
normal operation, oil pressure of the line compress the bladder and oil is
occupied in the oil space of the accumulator. When, pressure at the line drops,
the bladder is expanded, due to the inside gas pressure. So it pushes out oil
of space to the line and takes care momentary oil pressure fluctuation.
Emergency Situation In
Steam Turbine
Steam
Turbine is a critical rotating equipment. High temperature and pressure steam
is used to rotate the turbine at high speed. Mass of the rotating part is high. There is always chance of
severe misshapen leading to fatal accident and damage of high cost equipment.
Incase of any system goes wrong generation of power may be interrupted for a
longer period leading to heavy loss to the plant. So the power plant engineer
should be trained enough to face any emergency situation, at any time and
properly handled emergency situations.
1) Overspeed
Due
to failure of governing system the turbine speed may become dangerously high.
Rotor can rotate momentarily without damage up to 110% of rated speed. At
higher speed rotor stress increases. Due to high centrifugal forces the blades
which are fixed to the rotor may come out. Failure of blade root can cause
severe accident and damage to turbine.
To avoid dangerous over speed turbine is provided with mechanical and
electrical over speed trip arrangements. Tripping limits are set in such a way
that turbine speed does not exceed 110% of rated speed. These overspeed
tripping limits are to be checked regularly. Mechanical overspeed device is to
be set within set limit and checked at suitable intervals. At any circumstance
overspeed tripping limit is not to be bypassed. If overspeed tripping does not
work, immediately stop the turbine by applying emergency trip push button. For
the 18.5 MW turbine at Tata Sponge,
overspeed tripping limit is 7865 rpm.
2 ) Failure Of Lubrication Oil System :
Lubrication
Oil is used to lubricate and cool down bearing metal. Sometimes the lubrication
oil supply may be interrupted due to failure of pumps, leakage in oil line or
choking of oil filter. This condition may damage bearings and gear box. If such
an incident happens for any reason, the turbine is required to be stopped as
soon as possible. Low lube oil header
pressure tripping is incorporated with turbine to trip the turbine
immediately. If lube oil header pressure
becomes 1kg/cm2, oil supply is to be restored as early as possible.
After resuming oil supply, if possible, turbine is to be rotated manually to
find out any damage (inspect bearings).
3. High Vibration
Rotor
of the turbine rotates at high speed. Any deformation or unbalance of the rotor
produces high vibration. Sometimes deposits on blades and damage of any
rotating part may create heavy vibration. Damage of journal bearing may also
produce vibration. The moving and rotating parts of the turbine are closed
spaced. Due to disturbance in rotor shaft or differential expansion, there is
chance of rubbing. Rubbing creates high vibration and abnormal sound, so at any
case high vibration of turbine is not be overlooked. Incase of high vibration
the turbine should be stopped immediately and turbine internals to be inspected
to avoid further damage. High vibration protection in logic is incorporated
with turbine to trip the turbine when turbine front and rear journal bearing
vibration goes to 156 Micron and gear box front and rear journal bearing goes
to 340 microns.
4) High Bearing Temperature
High bearing temperature occurs due to
inadequate oil flow in the bearing or metal to metal contact in between bearing
and rotor. High temperature damages Babbitt material of the bearing. In case of
high temperature of the bearing, a turbine is required to be stopped. Oil
supply to bearing is to be checked and if required bearing is to be opened for
inspection. High bearing temperature protection logic is provided to turbine.
For different bearing 1150C is a tripping limit.
5) Failure Of Barring Device
When
turbine is stopped in hot condition, it is to be put on barring. In some
situation just after stopping turbine
barring gear may be found not working. It is not recommended to keep the
rotor in standstill condition. By any means rotor is to be rotated normally by
hand barring arrangements provided to change the rotor position by 180◦C
continuously.
6) High Condenser Hot Well Level
Due to problem in condensate extraction pumps,
sometimes the condensate cannot be evacuated from hot well. So hot well level
becomes high. In this situation there is possibility that water level in
condenser increases and enters into turbine through exhaust hood. Condenser
vacuum reduces drastically in this condition. If at any case water enters into
a running turbine it creates a serious situation and damages the turbine. Load
is to be reduced on turbine in this situation. If situation is not
controllable, turbine is to be stopped.
9) High Steam
Parameter
Like
low steam temperature and pressure, high steam temperature and pressure is not
desirable for turbine operation. High steam temperature may damage turbine as
the metrology of the turbine is designed for a particular temperature.
10) Low Condenser Vacuum
Due
to vacuum in condenser the steam from turbine is easily exhausted into
condenser. If vacuum inside the condenser drops, it restricts exhaust of steam
of turbine. This creates back pressure inside turbine. Vacuum may drop due to
failure in cooling water system, failure of ejectors, or leaking condenser air
line. Standby ejector or starting ejector is to be immediately taken into line.
Leaking air line is to be arrested promptly or cooling water supply to be
increased. If vacuum is not improved, the turbine is to be stopped immediately.
Low vacuum protection logic is provided to trip the turbine when condenser
vacuum drops to -0.4 kg/cm2.
11)
Failure Of Cooling Water Systems
Due to failure
of cooling water pumps or choking in cooling water circuit, cooling water
supply may be reduced or interrupted. In this case turbine exhaust steam cannot
be condensed. This will increase the pressure of the condenser and drop the
vacuum. Rapture disks of the condenser may rapture, heavy back pressure will be
created in turbine. In this case load is to be reduced first and care is to be
taken to normalize cooling water supply. If situation does not improve then
turbine is to stopped.
Black
Out maneuver Method for WHRB Power Plant
Both
the TG fails and Grid not available
: (BLACK OUT CONDITION)
1. In the above cases ( Total blackout condition ) ensure
availability of DG emergency power to
all the emergency drives of both the CPP within 10 seconds (i.e. Boiler main
steam stop valve, Auxiliary oil pump,
Barring gear, Emergency oil pump, Boiler feed pump discharge valve, CPP area
lighting & Jack oil pump & TG steam stop valve )
2. Ensure from field pressure gauge that lubrication continues in both the TG by
gravity method (oil flows from over head tank to all the TG bearings and
returns to main oil tank by drain header )
3. Ensure from HMI & field that Emergency oil pump is
running through DC power & oil
supply continues to all the bearings.
4. Start the Jack oil pump of TG.
5. If emergency power is not available within 10 seconds, then immediately contact
the Electrical Shift In Charge about the matter and try to resume emergency
power as quickly as possible, with the help of Shift In Charge CPP & Shift
In Charge Electrical.
6. After resuming
of emergency power, close main steam stop valve of all the three
Boilers and maintain the drum pressure
through start-up vent.
7. In blackout condition, ensure that Kiln stack cap will
remain 100% open till the availability of boiler feed pump. If stack cap is closed or
partially closed, then contact Kiln control rooms to open the same through
Shift In Charge CPP.
8. In blackout condition, all the boilers will be in hot
box-up condition.
9. Ensure emergency stop valve of TG is in closed
condition
10. Close the TG
inlet motorised valve .
11. Close all the
boilers feed pump discharge motorised valves.
12. After
resuming of emergency power, auxiliary
oil pump will start in auto mode. Ensure the same from field & HMI, then
stop the emergency oil pump from panel and put it in auto mode.
13. After resuming
of 1000kva DG, power start one feed pump of CPP-1 and supply water to all three boilers and maintain the drum level upto
40% .
such a great resource that you are providing and you give it away for free. I love seeing websites that understand the value of providing a quality resource for free. It's the old what goes around comes around routine.
ReplyDeleteThanks for sharing latest techniques.
DeleteMetering Pump Manufacturer in India
Dosing Pump Manufacturer in India | Chemical Dosing System | water treatment equipments
Thank you so much for taking the time to share such a nice information.
ReplyDeletereliable chemical dosing system
why drum level low in fuel cut off???/
ReplyDeletehii, Mujiyono Ath you have shared a informational article with us. You explained definition of boilers. its quality, system, accessories, startups etc. excellently. Please keep sharing like this.
ReplyDeleteBuilding automation
sir why we keep turbine tripping limit on 3rd extraction low pressure and high pressure?
ReplyDeleteFew years I spent as a steam turbine operator summarized here.Thanks for this.
ReplyDeleteRe-refining is a profitable opportunity since lube oil can be re-refined as many times as you like, therefore becoming a very
ReplyDeleteattractive business opportunity while safeguarding the environment.
Buy lube Oil Extraction Technology
ReplyDeleteThnq for sharing Informative news The Vasthi Water analyzer quality testing equipment is designed to give you field-ready durability with accurate results you can trust.
I came onto your blog while focusing just slightly submits. Nice strategy for next, I will be bookmarking at once seize your complete rises... Westinghouse Appliance Repair in San Diego
ReplyDeletesystem boiler service
ReplyDeleteWelcome to Rawda 365, Get the best heating boiler and plumbing service near me. We respond to all emergency services, boiler issues, heating problems and plumbing service. We offer the best system boiler leaking, boiler breakdown and plumbing repair service.
to get more - https://rawda365.co.uk/
Your writing skill is really appreciative, thank you so much for sharing this with us.
ReplyDeleteBoiler rental
Thank you for the information you shared, hopefully it will be useful to many people. send regards for success Jual Boiler Kapasitas 500 Kg
ReplyDeleteJual Boiler Gas
Fabrikasi Boiler Lokal
jual boiler 1 ton
Thank you for this information.This blog post is very helpful. we also provide best best service for Vaillant Boiler Service London. if you want our service so you can visit on our website.
ReplyDeleteThis is really helpful and informative, as this gave me more insight to create more ideas and solutions for my plan.keep update with your blog post.
ReplyDeletefire extinguisher refill
Nice articles and your information valuable and good articles thank for the sharing information elasto india
ReplyDelete